Parameters; Alarms And Warnings - Parker 250 Manuel D'utilisation

Masquer les pouces Voir aussi pour 250:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
x
To view the details of the event, press
:
ALx
1 Alarm code
2 Th ousands of hours
3 Hours
4 Dew point
5 Evaporation temperature
6 Compressor discharge temperature
z
é
Scrollwith
and
.
5.3

Parameters

Accessing parameters
z
é
Press
and at the same time
: the keypad now operates in Pa-
rameters MENU mode and the parameters can be scrolled with
é
and
.
List of parameters
A1
Sets the unit of measure for dew point in °C or °F.
A2/A3
Total hours of dryer operation= A3x1000+A2(display only).
A4/A5
Like A2/A3 but for hours of refrigeration compressor opera-
tion.
A6
Sets Hd Warning intervention temperature (see par. 5.4 in
List of alarm/warnings).
A7
Inhibits remote OFF command.
b1
Sets the dryer address for serial communications.
b2
Sets the serial communication speed
b3
Not available
b5
Refrigerant evaporation temperature
b7
Not available
b8
Compressor discharge (delivery) temperature
b9
Not available
C5
250
Dryer model: Mon = models
Mul = models
Note: if the C5 is set to = Mul in a monocooler dryer then
the warning ASE will occur. ASE is a warning for the mul-
ticooler models.
C7
Not available
C29
Must be set to "0".
C36
Operating logic of the alarm/machine status relay.
0 = relay energised when dryer is running, de-energised if
in warning/alarm status.
1 = relay de-energised when dryer is running, energised if
in warning/alarm status.
2 = relay de-energised when dryer is running, energised
in warning/alarm status.
C37
Not available
d1
Sets the seconds of condensate drain opening (if set in
TIMED mode).
d2
Like d1, but for seconds closed.
d3
Sets condensate drain operation mode:
z
- tIM = TIMED
- Con = EXTERNAL (24VAC)
Changing parameters
Aft er displaying the parameter, press
x
then press
to confi rm.
y
Press
to return to STANDARD mode.
5.4

Alarms and Warnings

Alarms cause the dryer to switch off .
Warnings only cause a signal.
In case of Alarm or Dew Point Sensor Warning (dSE),
the alarm code. In case of a Warning,
fault code and the dew point and WARNING LED comes on.
If an alarm occurs:
1) Identify and eliminate the cause;
z
2)press
to reset the alarm;
x
3) press
to restart the dryer.
If a warning without automatic reset occurs:
1) Identify and eliminate the cause;
z
2)press
to reset the warning.
List of alarm/warnings
HP
CP
LP
Ld
Lt
Ht
dSE
Hd
HSE
Sr
x
z
é
, change with
and
,
.
[
[
display
alternatively displays the
High Pressure alarm
Phases monitor alarm
Low Pressure alarm
Low Dew Point alarm
Low Evaporation Temperature alarm
High compressor Discharge Temperature alarm = T>248° F
(120°C)
Dew Point Sensor Warning
Th e measured temperature must return within its normal
range.
High Dew Point Warning
Automatic reset when the dew point = A6 - 4°F (2°C).
Discharge Temperature Sensor warning
Scheduled Maintenance warning
See par. 5.2 and 6.3