SMA SUNNY HIGHPOWER PEAK1 Instructions D'installation page 29

Masquer les pouces Voir aussi pour SUNNY HIGHPOWER PEAK1:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

SMA Solar Technology AG
Figure 2.22 Do not connect PV to ground
Figure 2.23: DC connection area
INFORMATION
Cables with multi-strand, fine-strand or extra
fine-strand conductors can be used for AC
connection (see figure 2.23). The cables must be
suitable for a temperature of at least 75°C.
When using fine-strand or extra fine-strand
conductors, bootlace ferrules must be used for the
connection.
Installation Guide
Figure 2.24 Cables with different conductors (from top to bottom):
multi-strand, fine-strand and extra fine-strand
1. Switch the PV load-break switch on the inverter to "Off"
and, if available, also on the PV array junction box.
2. Connect the PV cables from the PV array junction box
to the inverter. Ensure the correct polarity when doing
so.
3. All conductors must be properly attached with the
correct tool (screwdriver bit, length min. 50 mm) and
correct torque, see Section 5.4, page 45.
Cable requirements SHP 75-10
Figure 2.25 DC label SHP 75-10
SHP75-10-STP60-10-IA-xx-18
2 Installation
29

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sunny tripower 60

Table des Matières