wood logs perpendicular to the front. The fire should
burn with bright and lively flames.
Reload size
Chopped wood (diametre of 6-9cm)
Length: 25-35cm
Normal load size. 3,75 kg /h
When the fire end, close smoke damper in order to
store more warmth inside appliance.
Choice of Fuel
All types of wood, such as birch, beech, oak, elm, ash
and fruit trees, can be used as fuel in the stove. Wood
species have different degrees of hardness - the higher
the hardness of the wood, the higher the energy value.
Beech, oak and birch havest the highest degree of
hardness.
Attention! We do not recommend the use of fuel
briquettes / compact wood in our combustion chambers,
as these products may develop significantly higher
temperature than the combustion chamber can
withstand. Burning briquettes / compact wood is at your
own risk and can cause invalidity of the warranty.
Warning:
NEVER use impregnated wood, painted wood,
plywood, chipboard, rubbish, milk cartons,
printed material or similar. If any of these items
are used as fuel the warranty is invalid.
Common to these materials is that they during
combustion can form hydrochloric acid and
heavy metals that are harmful to the environment,
you and the stove. Hydrochloric acid can also
corrode the steel in the chimney or masonry in
a masonry chimney. Also, avoid burning bark,
sawdust or other extremely fine wood, apart from
when lighting a fire. This form of fuel can easily
cause a flashover that can lead to temperatures
that are too high.
Warning: Make sure the stove is not overheated
- it can cause irreparable damage to the product.
Such damage is not covered by the warranty.
Source: "Håndbok, effektiv og miljøvennlig vedfyring" by Edvard
Karlsvik SINTEF Energy Research AS and Heikki Oravainen, VTT.
6
4. Technical information:
- Salzburg C Basic
Minimum distances to
combustible materials
CO-content of flue gas @
13%O
2
Flue gas temperature
Thermal output
Thermal storage
capacity
Energy efficiency
Nominal heat output
during discharge period
(100%-25%)
Chimney draft
Length of wood logs
Weight
Load size (kg)
Max nr. loads
Loading interval
Nr. burning cycles per 24
hours
5. Before Installing a new fireplace
Several European countries have local
regulations for installation of fireplaces, which change
regularly. It is the responsibility of the client that these
regulations are complied with in the country/region
where the fireplace is installed.
Nordpeis AS is not
responsible for incorrect installation.
Important to check
(please note that this list is not exhaustive):
• distance from firebox to combustible/flammable
materials
• insulation materials/requirements between
fireplace surround and back wall
• size of floor plates in front of fireplace if required
• flue connection between firebox and chimney
• insulation requirements if flue passes through a
flammable wall
Chimney Draft
Compared to older models, the clean burning fireplaces
of today put significantly higher demands on the
chimney. Even the best fireplace will not work properly
if the chimney does not have the right dimensions or
GB
Back
50mm
Side
50mm
Ceiling
550mm
0,1%
140 °C
54,6 kWh
100% after 4,8 hrs
50% after 11,8 hrs
25% after 20,1 hrs
84,0%
3,6 kW
12 Pa
350 mm
936 kg
3,0 kg
5
1 / hour
1