Maximum limitation
69
of room temperature
Effect of room tem-
70
en
perature
Boost of room tem-
71
perature setpoint
with boost heating
Parallel displace-
72
ment of heating
curve
Type of heating
73
curve adjustment
Block "3-position actuator for heating circuit"
Maximum limitation
81
of flow temperature
Minimum limitation
82
of flow temperature
Maximum rate of
83
increase of flow
temperature
Excess flow tem-
84
perature mixing
valve
Actuator running
85
time
Building Technologies
--.- °C
(--.- / 0...35)
°C
...................
4
(0...20)
.........................
5 °C
(0...20)
°C
...................
0.0 °C
°C
(−4.5...+4.5)
...................
0
(0...2)
.........................
--- °C
(--- / 0...140)
°C
...................
--- °C
(--- / 0...140)
°C
...................
--- °C/h
(--- / 1...600)
°C/h
..............
10 °C
(0...50)
°C
...................
120 s
(30...873)
......................
74 319 0619 0 a
Setting --.- = limitation deacti-
vated
Function possible only with
room unit / room temperature
sensor
Gain factor for effect of room
temperature
Function possible only with
room unit / room temperature
sensor
Value in °C room temperature
0 = analog adjustment
1 = digital adjustment on the
controller and via bus
2 = digital adjustment via bus
only
Setting --- = function deacti-
vated
No safety function
Setting --- = function deacti-
vated
Setting --- = function deacti-
vated (function prevents crack-
ing noise in piping)
Setpoint boost for precontroller
in interconnected plants
s
17.04.2008
50/288