Télécharger Imprimer la page

Siemens RVL482 Mode D'emploi page 52

Masquer les pouces Voir aussi pour RVL482:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 66
en
100 Switching differen-
tial bypass pump
Block "Setpoint of return temperature limitation"
101 Setploint of return
temperature limita-
tion / bivalent start-
ing point
Block "Type of limitation of return temperature"
102 Type of limitation of
return temperature
Block "Bivalent maximum limitation of return temperature"
103 Maximum setback
of boiler temp. set-
point
104 End point bivalent
Building Technologies
6 °C
(1...20)
°C
...................
--- °C
(--- / 0...140)
°C
...................
0
(0 / 1)
.........................
10 °C
(1...50)
°C
...................
60 °C
(0...140)
°C
...................
74 319 0619 0 a
2 = bypass pump parallel to
burner stage 1
3 = bypass pump with control
via return temperature
sensor B7
Function is of importance only if
operating line 99 = 3
Entry --- = function deactivated
For explanation of "bivalent",
refer to operating lines 103 and
104
0 = minimal
1 = maximal
If the plant has a bypass pump
controlled via return tempera-
ture sensor B7, this setting is
inactive. In that case, the type of
limitation is always minimum
limitation
BoSp
OpL103
OpL101 OpL104
TRt
BoSp = Boiler setpoint
OpL
= Operating line
TRt
= Return temperature
17.04.2008
52/288

Publicité

loading