7.3.3 Checking the residual current device

Fig.: 24. Check the residual current device
The residual current device can be checked for function-
ality using the multi-function button without opening the
housing.
f Insert a flat screwdriver with a blade width of 8 to 10
mm into the slot of the multi-function button.
f Turn the multi-function button 90° counterclockwise.
f Press the multi-function button for about two seconds
(> 5mm).
Is the residual current device functional?
9
The residual current device triggers.
9
The fault indicator on the LED info field flashes red.
f Switch the residual current device on again.
Î "7.3.2 Restarting residual current devices and miniature
circuit breakers"
24
7.4

Stop button

Only available for the equipment variants Start (E),
Standard E and Basic E.
Terminating charging and acknowledging faults
Fig.: 25. Terminating charging and acknowledging faults
Terminating a running charging process (only for devices
without key switch) and acknowledging faults.
f Press the stop button (about 10 mm).
9
The charging process is terminated and the charging
plug in the device is unlocked.