5.3 On-site installation

T
T
DANGER
Fire hazard due to device overload.
There is a fire hazard due to overloading of the device
caused by unsuitable circuit breaker and supply line.
f Route the supply line and the circuit breaker according
to the technical data of the device.
The installation of a device in a supply grid in the
disturbance sources e.g. a frequency converter
can cause malfunction or termination of the
charging process.

5.3.1 Supply line

f Design of the supply line according to the rated current.
Î "4. Technical data"
When dimensioning the supply line (cross section
and cable type), always ensure the following local
conditions:
„ Type of installation
„ Cable parameters per unit length
„ Line length
14

5.3.2 Fuse protection rating

Depending on the version, the device is equipped with a
type B residual current device (RCD) and a miniature circuit
breaker (MCB) according to the table below.
Version
Start (E), Standard E, Basic E
Basic R
Light, Pro, Basic
Miniature circuit breaker (MCB)
For the versions Start, Start E,
Standard E, Basic E und Basic R, the required miniature cir-
cuit breaker (MCB) must be provided on site.
The miniature circuit breakers must be dimen-
sioned according to the specifications on the type
plate, the required charging power, the supply
line (line length, cable cross-section) to the device
and national regulations.
Residual current device (RCD)
T
T
DANGER
Risk of injury from electric shock
Residual current devices (type B) sensitive to universal cur-
rents may not be installed behind residual current circuit
devices (type A) which are sensitive to pulse currents. The
type A trigger function can be affected by type B so that
they cannot be switched off even if fault currents occur.
f Always connect a type B residual current device to a
type A residual current device.
RCD type B
MCB
-
-
X
-
X
X