6
Commissioning
6.1
Basic settings via DIP switch
Changes made via the DIP switches only
take effect after restarting the product.
u Disconnect product from voltage if necessary.
6.1.1 Configuring the product
The tasks described in this section may only
be carried out by a qualified electrician.
In the top section of the housing, there are two 8-
pin DIP switches, with which the device can be con-
figured. In the delivery state, all DIP switches are
switched off ("OFF"). On delivery, the product is
ready for connection.
Fig. 9: DIP switch (delivery state)
1
Bank S1
2
Bank S2
The following functions can be set via the DIP
switches:
Bank S1
DIP
Function
switch
1
LED display colour scheme
n "OFF":
n "Standby" symbol = blue
n "Charging" symbol = green
n "ON":
n "Standby" symbol = green
n "Charging" symbol = blue
2
Unbalanced load limitation
n "OFF": Unbalanced load limitation off
n "ON": Unbalanced load limitation on
3
Authorisation
n "OFF": No authorisation (Autostart)
n "ON": Authorisation via the enable in-
put
4, 5, 6,
Without function
7, 8
Bank S2
1
DIP
Function
switch
1, 2, 3
Max. charging current
2
4, 5
Reduced charging current when down-
grade input is energised
6,7,8
Without function
6.1.2 Setting the maximum charging current
The tasks described in this section may only
be carried out by a qualified electrician.
The maximum charging current of the charging
point can be set via DIP switches 1, 2 and 3 on bank
S2.
AMTRON® Compact 2.0 22
The maximum charging current can be set to 6 A,
10 A, 13 A, 16 A, 20 A, 25 A or 32 A.
EN
17