MAINTENANCE
Warning
This unit restarts automatically.
Before any intervention on the unit, operator must make sure
that the main switch is safely secured.
Recommendations
If the unit is stopped for long periods of time, the fan motors should be run for
at least two hours each week.
Every month, carry out an operating check on:
Cleanliness of coil
Refrigerant level
Minimum every year:
Clean the gas cooler
Instructions or recommendations appearing in the various technical advice notes
and manufacturer's service manuals should be followed precisely. Please
contact our Technical Department for any additional information.
Cleaning
Coils should preferably be cleaned with:
Compressed air
By brushing with non-metallic materials
Avoid all aggressive detergents which may cause eventual corrosion.
Replacement parts
References of replacement parts are given by After sales department (+46 920
245 450).
Operating instructions for maintenance
For all maintenance operations, the following instructions must be followed:
Unit door must only be opened after the main switch has been cut-off
and the fans have stopped completely.
The safety HP can be accessed when the door is opened.
Then, access to service ports for connecting the pressure gauge is
possible.