500 mm
1200 mm
250 mm
The QUIETCO2OL
is intended for
outdoor installation
500 mm
–
Vibration should be reduced by
a platform or anti-vibration pad
for avoiding transmission of
vibration to the floor and wall.
–
To avoid falling, secure the
refrigeration unit by using
anchor bolts. (Use all securing
positions)
–
The refrigeration unit must be
installed with an inclination
angle 1°or below. If devices are
used in a seismic area, then the
installer must apply all
necessary rules.
–
Enough free space all around
the refrigeration equipment
should be provided to facilitate
maintenance operations.
–
The heat exchangers must be
installed in locations free of any
external dust or other pollutants
from the neighbourhood which
could obstruct or clog the coils.
–
If devices are used in a
corrosive area (sea side,
pollutant gas, etc.), make sure
that appropriate anticorrosion
protection has been provided.
–
The distance between the
QUIETCO2OL unit and the
evaporator must not exceed 15
meters.