CONTROL FUNCTIONS
Alarm list
Alarm code
Display description
ALU02
Regulation probe(s) missing
Discharge temperature probe
ALA01
broken or disconnected
External temperature probe
ALA03
broken or disconnected
Suction pressure probe
ALA24
broken or disconnected
Suction temperature probe
ALA25
broken or disconnected
Gascooler outl. temp. probe
ALA43
broken or disconnected
ALB07
Fans common overload
ALB15
High suction pressure alarm
ALB16
Low suction pressure alarm
ALC01
Alarm 1 compressor 1
Power + nβ device offline
ALP01
Compressor start failure
ALP03
(tempt.: / max.:)
High discharge gas
ALP05
temperature
Low pressure differential
ALP06
(insufficient lubrication)
Warning setpoint HPV
ALT17
gascooler press. too different
from current setpoint
HPV alarm high receiver
ALT18
pressure
Warning high pressure
ALW01
prevent
ALW05
Warning fans inverter
Warning an error occurred
ALW15
during auto-configuration
Power + nβ device offline
ALW24
Compressor start failure
ALW26
(tempt.: / max.:)
High discharge gas
ALW28
temperature
Low pressure differential
ALW29
(insufficient lubrication)
ALW35
Low suction temperature
Reset
Delay
Automatic
Not present
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
Config.
Automatic
Config.
Automatic
Config.
Man./Autom.
Config.
Automatic
Not present
Semiautomatic Not present
Automatic
Not present
Automatic
Config.
Automatic
Config.
Automatic
Not present
Automatic
Config.
Automatic
Not present
Automatic
Not present
Semiautomatic 2 s
Semiautomatic Not present
Automatic
10 s
Automatic
Settable
Automatic
Not present
Action
Shutdown Unit
Related functions disabled
Related functions disabled
Related functions disabled
Related functions disabled
Related functions disabled
-
-
-
Shutdown compressor
Related functions disabled
5 retries, shutdown
compressor
Shutdown compressor
Shutdown compressor
Related functions disabled
Related functions disabled
Related functions disabled
-
-
Shutdown compressor
-
-
-
Related fuctions disabled