COMMISSIONING
–
Do not use other than the designated refrigerant (for
charging, adding or recharging).
–
Prior to electrically connect the facility, make sure
that the AC power line voltage and frequency
ratings correspond to the indications on the
identification plate and the power voltage is within
a tolerance of + 10 % with respect to the rated
value.
–
Specific protection is provided according to the
neutral system.
–
Any on-site wiring must comply with the legal
standards in force in the country of installation
(including grounding).
–
Before turning on a device, make sure that:
–
the electric connections have been correctly
made
–
the clamping screws of the various
terminals are correctly tightened
–
Check the possible presence of locking
devices of compressor antivibration
elements, and remove them, if they exist.