CONTROL FUNCTIONS
Protective functions
Compressors stops when:
High pressure exceeds 108 bar.
Low pressure is below 15 bar.
BLDC Power + Alarm. See display information. Compressor
auto reset.
5 times before alarm becomes manual.
Compressor out of envelope alarm. Compressor auto reset.
5 times before alarm becomes manual.
Gas cooler fan is protected by internal temperature sensor.
All alarms are visible after pressing the flashing red warning triangle.
Hold down to reset. Example here:
disconnected.
Restarts with manual reset.
Automatic reset.
Automatic reset.
suction pressure probe broken or