Télécharger Imprimer la page

Lutron GRAFIK Eye. NTGRX-4S Instructions D'installation page 6

Commandes murales utilisées avec les systèmes des séries 3000 et 4000

Publicité

Les langues disponibles
  • FR

Les langues disponibles

7. Wiring must be done in a daisy-chain and 1-to-1 configuration
(please see Installer's Guide included with Control Unit for
more information). Each Wallstation terminal will accept up to
two #18 AWG (1.0 mm
2
) wires.
3000 Series System Wiring. Connect four #18 (1.0 mm
twisted pair wires to the Wallstation's terminal block. Please
note that the terminal marked "D" on the EGRX Wallstation is
not used for GRAFIK Eye 3000 Series Control Unit wiring.
4000 Series System Wiring. Connect two #18 (1.0 mm
shielded, twisted pair wires to terminals 3 and 4 of the
Wallstation's terminal block. Shielding must be connected as
shown, but do not connect to Earth/Ground or Wallstation.*
2
Two #12 AWG (2.5 mm
) power wires will not fit in the terminal
blocks, however, #12 AWG (2.5 mm
voltage drop on the wire. Use the diagram shown at right to
make the connections in the wallbox.
8. Mount Wallstations. Attach faceplate by pressing in at each
corner, one corner at a time. Restore power.
Wallbox
Mounting
Frame
Typical Mounting Diagram
(see next page for EGRX Mounting)
Installation Instructions
2
)
2
)
2
) is necessary due to
Adapter
Faceplate
Daisy-Chain Configuration
4
3
2
1
3000 Series System Wiring
4
3
2
1
1 #18 AWG
(1.0 mm
* Please note that drain wires are connected to the terminal marked
"D", when available.
4000 Series System Wiring
6
4 twisted pair,
#18 AWG
(2.5 mm
2
)
Drain
2 #12 AWG
(2.5 mm
2
)
2 #12 AWG
2
)
(2.5 mm
2
)
Occupant Copy

Publicité

loading