Installation Instructions
Occupant Copy
For Programming, see the QSE-IO Control Interface Programming Guide
PN 040391 at www.lutron.com/qs
Overview
The QSE-IO contact closure interface provides integration
with third-party equipment requiring contact closure input /
output, including occupancy and vacancy sensors; motorized
projection screens, skylights, and window shades; AV
equipment; security systems; movable partition walls; and
timeclocks. One QSE-IO interface provides five (5) dry contact
closure outputs.
For complete functionality, programming instructions, and
detailed DIP switch settings, see the QSE-IO Programming
Guide, PN 040391, at www.lutron.com/qs.
QS Link Limits
• The QS wired communications link is limited to 100 devices
and 100 zones. Each QSE-IO control interface counts as 1
device and 5 zones.
• Each QSE-IO control interface consumes 3 power draw units
(PDU) on the QS link. Refer to the QS Link Power Draw Units
Specification Submittal (Lutron PN 369405, at
www.lutron.com) for more information.
• The maximum wiring length for the QS link is 2000 ft (610 m).
Dimensions
shown as in (mm)
Terminal blocks
on this side
3.75 in
(95 mm)
1.0 in
(27 mm)
®
Please Read
2.5 in
(64 mm)
Mounting Holes
5.25 in
(134 mm)
QSE-IO Control Interface
SELV / PELV / NEC
R
Class 2 Device 24–36 V- 100 mA
Compatible Components
The following devices are compatible with the QSE-IO.
For more information on each, refer to
www.lutron.com/qs.
• GRAFIK Eye
R
QS control units
• seeTouch
R
QS wallstations
• Sivoia
QS shades
R
• QS Interfaces (contact closure, Ethernet/RS232)
• Quantum
R
system
• Energi Savr Node
units
T
• QS Sensor Module
• QS Keyswitch
LEDs and addressing
switches on this side
4.25 in
Mounting Hole Detail
(108 mm)
0.25
(6 mm)
#6 or #8 (M3 or M4)
screw recommended
(not included)
0.1875 in
(5 mm) dia.
0.3125 in
(9 mm) dia.
0.1875 in
(5 mm) dia.