Types 2100, 2101, 2103
Option:ThreadedNipple
8.1.2. Installation and start-up
→
Screw the threaded nipple ① into the actuator cover Ⓒ;
tightening torque: 10 Nm.
NOTE!
If the proximity switch is screwed in too deeply, it may be
damaged by the switching movement of the valve!
• Align the depth to which the proximity switch is screwed in
to the upper end position of the actuator (note the switching
distance of the proximity switch).
→
To install the proximity switch, move the actuator to the upper
end position:
Apply the pilot pressure to connection 1.
→
Screw the proximity switch into the threaded nipple ①.
→
Secure the screw-in depth of the proximity switch with a lock
nut (normally included in the scope of supply of the proximity
switch).
→
Check the valve for function and leaks.
Fig. 10: Actuator D (50), threaded nipple
English
C Actuator cover
C
Required parts
1 Threaded nipple
19