6.2.1. Tasks before Installation
DANGER!
Risk of injury from high pressure!
• Before making alterations to the devices, switch off the pressure
and vent the lines.
Interrupt the flow of medium.
Switch off the pilot air.
Empty the valve body.
Unscrew the transparent cap Ⓐ from the actuator cover Ⓓ.
Remove O-ring Ⓒ.
DANGER!
Risk of injury from high pressure!
Without the transparent cap, the actuator blows freely upward
when the pilot pressure is applied to the wrong connection.
• Apply the pilot pressure for control functions A and I only on
connection 1.
To remove the optical position indicator Ⓑ, move the actuator to
the upper end position:
Apply the pilot pressure to connection 1.
Unscrew the optical position indicator Ⓑ from the spindle
extension Ⓔ.
6.2.2. Installation and start-up
Screw the threaded nipple ③ into the actuator cover Ⓓ;
tightening torque: 25 Nm.
Turn the threaded spindle ① to adjust the upper end position.
Secure the threaded spindle ① with nut ②.
Check the valve for function and leaks.
Fig. 4:
Actuators M (70), N (90) and P (130), max stroke limit
English
D Actuator cover
Required parts
D
1 Threaded spindle
2 Nut
3 Threaded nipple