EN
A
PICTURES
[1] animeo IB+ Building Controller
B
MOUNTING
[1] DIN-rail version
1.
Electrical cabinet
C
WIRING
Finish wiring and connect power supply
[1] Keep to minimum distance
[2] Tool for all terminals
[3] Wiring diagram Building Controller
A.
Mains
1.
L = Phase conductor
2.
N = Neutral conductor
3.
PE = Protective conductor
B.
Malfunction indication (output)
C.
Central switch (input)
D.
HVAC cooling (input)
E.
HVAC heating (input)
F.
Alarm (input)
G.
PC bus (in-/output)
H.
Sensor bus (in-/output)
I.
Somfy IB and IB+ control wire (output)
(see cable type and length in table on page 6)
[4] The RS485 2-wired network consists of two to six
devices depending on the version. They can be
wired in any order. At the beginning and at the
end of the wire network a 120 Ohm resistance is
essential.
[5] To operate two 8 zone Building Controllers in master
slave modus the clamps A and Y, as well as B and Z
of the slave 5 Building Controller have to be bridged
to the PC bus clamps.
[6] Wiring API (application programming interface)
1.
USB/RS485 interface (plug in only after software
has been installed on PC!)
VERDRAHTUNG KABELING KAAPELOINNIT
Anschluss an ...
Forbindelse til ...
Connection to ...
220 - 230 V AC
100 - 120 V AC
Error out
Building in
Cool in
Heat in
Alarm in
PC Bus
Sensor Bus
IB+ bus
* see C [6] 2 and 3 / RS232 / RS485 converter animeo Ref. 9011217
** see C [6] 1 USB / RS485 converter animeo Ref. 9012519
Leitung
Kabel
Cables
Min.: 3 x 1.5 mm
/16 AWG
2
Max.: 3 x 2.5 mm
/13 AWG
2
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm
/13 AWG
2
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm
/13 AWG
2
Min.: 2 x 0.6 mm/22 AWG
Max.: 2 x 2.5 mm
/13 AWG
2
Min.: 2 x 0.6 mm/22 AWG
Max.: 2 x 2.5 mm
/13 AWG
2
Min.: 2 x 0.6 mm/22 AWG
Max.: 2 x 2.5 mm
/13 AWG
2
Min.: 4 x 0.6 mm/22 AWG
Max.: 4 x 0.8 mm/20 AWG
Min.: 2 x 0.6 mm/22 AWG
Max.: 2 x 0.8 mm/20 AWG
Min.: 4 x 0.6 mm/22 AWG
Max.: 4 x 1.5 mm
/16 AWG
2
1.
Blue
2.
Red
3.
Black
4.
White
2.
RS232/RS485 interface; model with 2 sliding
switches
3.
RS232/RS485 interface; model with 3 sliding
switches
D
CONFIGURATION/STATUS INDICATION
[1] New start of Building Controller: Keep reset button
pressed > 5 secs.
[2] Reset Building Controller in delivery status:
Voltage off: keep Reset button pressed
Voltage on: keep Reset button pressed > 5 secs.
[3] Status indication
1.
Power supply: green LED permanently active
2.
Malfunction indication: red LED is blinking
3.
Main (master) switch: receiving a movement
command the LED is active for 1 second; Red on
UP order, orange on STOP order, yellow on DOWN
order
4.
HVAC cooling: green LED is active permanently
when cooling is active
5.
HVAC heating: green LED is active permanently
when heating is active
6.
Alarm (see help file in the animeo Operating
Software): red LED is active permanently
[4] Somfy IB control line
Movement command with priority: LED shines red as
long as the command is active. On movement com-
mand the LED shines for 1 second; red on UP order,
orange on STOP order and yellow on DOWN order.
[5] Somfy IB+ control line
In a position movement command the LED flashes
red for 1 second.
[6] Building Controller is in slave process, if the four
LED's flash in 1 second intervals.
Verdrilltes Adernpaar
Parsnoet
Twisted pair
-
-
-
-
-
-
Required
Required
Recommended
animeo IB+ BUILDING CONTROLLER. REF. 5007653E -
Max. Länge
Maks. længde
Max. distance
100 m/330 ft
50 m/165 ft
150 m/500 ft
150 m/500 ft
150 m/500 ft
500 m/1650 ft* RS485
10 m/33 ft** USB
500 m/1650 ft
1000 m/3300 ft
6/12