ABB PVS800 Manuel D'exploitation page 16

Masquer les pouces Voir aussi pour PVS800:
Table des Matières

Publicité

12
No.
Name/Value
OFF
MAX RMS VOLT
MIN RMS VOLT
POS SEQ VOLT
41.03
GS U/Un LEVEL 1
[41.04]...200%
41.04
GS U/Un LEVEL 2
[41.05]...[41.03]%
41.05
GS U/Un LEVEL 3
[41.06]...[41.04]%
41.06
GS U/Un LEVEL 4
0...[41.05]%
41.07
GS IQREF LEVEL 1
0...100%
41.08
GS IQREF LEVEL 2
0...100%
41.09
GS IQREF LEVEL 3
0...100%
41.10
GS IQREF LEVEL 4
0...100%
41.11
RT IQREF
0...100%
41.12
RT IQ RAMP UP
0...100 s
Update notice
FbEq
Description
0
Grid support function is disabled.
1
Input for the grid support function is the highest RMS AC voltage,
either phase or main.
2
Input for the grid support function is the lowest RMS AC voltage,
either phase or main.
3
Input for the grid support function is a positive sequence of the AC
voltage.
Defines grid support level 1. When the voltage falls below this
level, the grid is supported by feeding capacitive current as defined
by
41.07 GS IQREF LEVEL
1 = 1%
Grid support voltage level 1.
Defines grid support level 2. When the voltage falls below this
level, the grid is supported by feeding capacitive current as defined
by
41.08 GS IQREF LEVEL
1 = 1%
Grid support voltage level 2.
Defines grid support level 3. When the voltage falls below this
level, the grid is supported by feeding capacitive current as defined
by
41.09 GS IQREF LEVEL
1 = 1%
Grid support voltage level 3.
Defines grid support level 4. When the voltage falls below this
level, the grid is supported by feeding capacitive current as defined
by
41.10 GS IQREF LEVEL
1 = 1%
Grid support voltage level 4.
Defines the reactive current reference point for
LEVEL 1
in percent of
1 = 1%
Grid support reference level 1.
Defines the reactive current reference point for
LEVEL 2
in percent of
1 = 1%
Grid support reference level 2.
Defines the reactive current reference point for
LEVEL 3
in percent of
1 = 1%
Grid support reference level 3.
Defines the reactive current reference point for
LEVEL 4
in percent of
1 = 1%
Grid support reference level 4.
1 = 1%
Defines an external reactive current reference during a voltage dip.
If the value differs from 0, the reactive current reference defined by
parameters
41.03...40.10
Reactive current reference
10 = 1 s
Defines the ramp time from zero to nominal current
NOM
CURRENT) for the reactive current reference.
Ramp time
1.
2.
3.
4.
41.03 GS U/Un
04.05 CONV NOM
CURRENT.
41.04 GS U/Un
04.05 CONV NOM
CURRENT.
41.05 GS U/Un
04.05 CONV NOM
CURRENT.
41.06 GS U/Un
04.05 CONV NOM
CURRENT.
is bypassed.
Def.
100%
50%
25%
15%
0%
100%
100%
100%
0%
(04.05 CONV
0.04 s
T
R
R
R
R
R
R
R
R
R
R