Analogue inputs
analogue conversion
type
maximum number
time constant for each input
precision
classifi cation of the measuring
circuits (CEI EN 61010-1)
WARNING: the 21 Vdc available at the +Vdc terminal (J2) can be used to power any active probes, the maximum current is 150 mA,
thermally protected against short-circuits. To supply the ratiometric 0 to 5 V probes, use the +5V
Analogue outputs
type
maximum number
power supply
resolution
maximum load
precision
Digital outputs
type
relay
maximum number
8: SMALL; 13: MEDIUM; 18: LARGE; 27: EXTRALARGE N.C.; 29: EXTRALARGE N.O.
For the requirements refer to Figs. 3 to 5 (reference NO*, NC* and C*). Note the presence of outputs with changeover contacts kept
separately (that is, without the poles shared between different outputs). Groups from 2 to 5 outputs have 2 "common" poles for easy
assembly.
Make sure that the current running through the common terminals does not exceed the rated current of each individual terminal, that is 8A.
Insulation distance
the outputs can be divided into groups. There is double insulation between groups (between cells in the table).
Note: the relays in the same group must have the same power supply (24 or 230 Vac).
Makeup of the groups
version
SMALL
Type of relay
MEDIUM
Type of relay
LARGE
Type of relay
EXTRALARGE N.O.
Type of relay
EXTRALARGE N.C.
Type of relay
Note: the relays in the individual cells of the table have basic insulation between them, while between groups (cell-cell)
there is double insulation.
Changeover contacts
1: SMALL (relè 8); 3: MEDIUM e EXTRALARGE N.O./N.C. (relè 8, 12 e 13); 5: LARGE (relè 8, 12, 13, 14 e 15)
Switchable power
warning: the relay outputs have different characteristics according to the model of pCO
relay
type A
relay
type B
relay
type C
SSR outputs
1: SMALL (output 7); 2: MEDIUM - EXTRALARGE N.O./N.C. (outputs 7, 12); 3: LARGE (OUTPUTS 7, 12, 14)
operating voltage 24 Vac/Vdc; maximum power: 10 W
+050003290 - 1.4 - 29.09.2006
10 bit A/D converter in the CPU
universal: (inputs B1, B2, B3, B6, B7, B8) CAREL NTC temperature sensor (-50T90°C; R/T 10 kΩ at 25°C),
HT NTC 0T150°C, voltage: 0 to 1 Vdc, 0 to 5 V ratiometric or 0 to 10 Vdc, current: 0 to 20 mA or 4 to 20 mA,
selectable via software. Input resistance in 0 to 20 mA= 100Ω
passive: (inputs B4, B5, B9, B10) CAREL NTC temp. sensor (see universal type),
PT1000 (-100T200°C; R/T 1000 Ω at 0°C) or voltage-free digital input (5 mA), selectable via software;
5, 8, 10, on the SMALL, MEDIUM and EXTRALARGE N.O., LARGE and EXTRALARGE N.C. boards respectively
0.5 s
± 0.3 % of full scale
Category I
0 to 10 Vdc optically-isolated
4, 4, 6, on the SMALL, MEDIUM and EXTRALARGE N.O./N.C., LARGE boards respectively
external 24 Vac/Vdc
8 bit
1 kΩ (10 mA)
± 2 % of end scale on outputs: Y1, Y2, Y3 and Y4
-2%/+5% of end scale on: Y5 and Y6
type of relay: SPDT, 2000 VA, 250 Vac, 8 A resistive
3
pCO
approval: UL873: 2.5 A resistive, 2 A FLA, 12 A LRA, 250 Vac, C300 pilot duty (30000 cycles)
EN 60730-1: 2 A resistive, 2 A inductive, cosϕ= 0.6, 2(2) A (100000 cycles)
type of relay: SPDT, 1250 VA, 250 Vac, 5 A resistive
pCO
3
approval: UL873: 1 A resistive, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cycles)
EN 60730-1: 1 A resistive, 1 A inductive, cosϕ= 0.6, 1(1) A (100000 cycles)
type of relay: SPDT, 1250 VA, 250 Vac, 5 A resistive
pCO
3
approval: UL873: 1 A resistive, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty (30000 cycles)
relays with same insulation
1...7
8
-
A type
A type
1...7
8
9...13
A type
A type
A type
1...7
8
9...13
A type
A type
A type
1...7
8
9...13
A type
A type
A type
1...7
8
9...13
A type
A type
A type
EN 60730-1: 1 A resistive, 1 A inductive, cosϕ= 0.6, 1(1) A (100000 cycles)
15
(Imax: 60 mA) present at terminal J24.
REF
-
-
-
-
14...18
-
A type
14...16
17...20
21...24
B type
B type
B type
14...16
17...20
21...24
C type
C type
C type
3
25...29
B type
25...27
C type
english