English
Description
Operating system
* USB 3.0 interfaces cannot be used!
6.2.3. Preparations
The alarm switchgear must be installed and
connected fully as described in the "Installation"
section.
The SIM card must not be inserted yet and the
alarm switchgear must not be connected to the
PC yet.
6.2.4. Installing the software and configuring the GSM
module
See the extended installation and operating
instructions on the enclosed CD-ROM for all other
details on configuring the GSM module and the
software.
7. Commissioning
POTENTIALLY fatal danger due to electrical
voltage!
Incorrect electrical connections can cause fa-
tal electric shocks! Electrical connections may
only be inspected by a qualified electrician
approved by the local energy supply company,
in accordance with locally applicable regula-
tions.
The "Commissioning" section contains all the
important instructions for operating personnel on
commissioning and operating the alarm switch-
gear safely.
Always keep this manual either by the alarm
switchgear or in a place specially reserved for it,
where it is accessible for all operating personnel
at all times. All persons working on or with the
alarm switchgear must have been provided with
this operating and maintenance manual and have
read and understood it.
In order to prevent damage or serious injury when
commissioning the alarm switchgear, the follow-
ing points must always be observed:
• The alarm switchgear must be installed as de-
scribed in the "Installation" section and in accord-
ance with the applicable national regulations.
• The alarm switchgear must be properly fused and
earthed.
• All safety devices and emergency cut-outs must
be connected and inspected to ensure that they
are working properly.
• The alarm switchgear is suitable for use under the
specified operating conditions.
7.1. Connections
The signal transmitters on the digital inputs and
the controls/components at the alarm outputs
(changeover contacts) are connected poten-
tial-free.
26
Minimum re-
Recommended
quirement
requirement
MS Windows XP, SP2
MS Windows Vista
MS Windows 7, 32/64 bit
MS Windows 8, 32/64 bit
The signal transmitters are installed accordingly in
the operating space to monitor the levels and the
switching points were tested.
7.2. Operation in potentially explosive areas
The alarm switchgear may not be installed or used
in potentially explosive areas.
RISK of fatal injury due to explosive atmos-
phere!
The alarm switchgear is not Ex-rated. Opera-
tion in potentially explosive areas will lead to
explosions! The alarm switchgear must always
be installed outside potentially explosive
areas!
7.3. Switch on the alarm switchgear
As soon as the battery is connected or the mains
connection is established, the alarm switchgear
starts.
The LEDs in the housing cover signal proper func-
tion as follows.
DrainAlarm
Symbol
Colour
LED is lit up: Mains voltage is present,
Green
battery is charging
DrainAlarm GSM
Symbol
Colour
LED is lit up: Mains voltage is present,
Green
battery is charging
GSM module: LED is lit up
Green
Ready for operation after 2 minutes
GSM module: Status LED
Continuous flashing: Start procedure
Yellow
Is lit up: Connected to the mains
Flashes twice: SIM card not available
7.4. Conduct during operation
When operating the alarm switchgear, always
follow the locally applicable laws and regulations
for work safety, accident prevention and handling
electrical products. To help ensure safe working
practice, the responsibilities of employees should
be clearly specified by the operator. All personnel
are responsible for ensuring that regulations are
observed.
LEDs on the front of the housing are used to op-
erate the alarm switchgear, display the operating
status, and signal alarms and faults. The housing
cover must not be opened during operation.
DANGER due to electrical voltage!
When working on the uncovered alarm
switchgear, there is a risk of fatal electric
shocks. Only operate the alarm switchgear
with the cover closed!
COMMISSIONING