Reset Confi Guration; Faults And Troubleshooting - Comelit iPower 8595 Mode D'emploi

Masquer les pouces Voir aussi pour iPower 8595:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 44
Reset confi guration
32
Caution: this operation will restore all the factory settings, deleting
all changes made.
1. Enter the Installer menu (See point 19).
2. Select the Program Monitor menu using the
press the
button to enter.
INSTALLER MENU
Program monitor
3. Select the Reset confi guration menu using the
press the
button to enter.
PROGRAM MONITOR
Logical address
Set bracket
Information
Reset configuration
Select network type
4. Press
to confi rm.
RESET CONFIGURATION
Continue?
33
No connection with the internal unit.
,
buttons and
Solutions:
} Wait 1 minute.
} Make sure that the secondary monitor has the same address as
the main monitor in the relevant residential unit (point 22).
} Make sure that the main monitor is receiving power (point 10).
} Make sure that the correct password has been entered (point 20).
,
buttons and
} Make sure that the installation distances have been observed
(point 8).
No connection with the external unit.
Solutions:
} Wait 1 minute.
} Make sure that the external unit is wired correctly (point 2).
} Make sure that the external unit is receiving power (point 9).
} Make sure that the bridge Art. 1398 is wired correctly (point 7A,
7B, 7C).
} Make sure that the password for bridge Art. 1398 is the same as
the password for the power supply unit of the monitor in the same
residential unit.
} Make sure that the installation distances have been observed
(point 8).

Faults and troubleshooting

No Signal Detected
No Signal Detected
EN
43

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ipower 8596

Table des Matières