Annexe; General Considerations - Grundfos TPE 2000 Serie Notice D'installation Et De Fonctionnement

Table des Matières

Publicité

Annexe

25. Installation in the USA and Canada
In order to maintain the UL/cURus approval,
Nota
follow these additional installation instructions.
The UL approval is according to UL508C.
25.1 Electrical connection
25.1.1 Conductors
Use 140/167 °F (60/75 °C) copper conductors only.
25.1.2 Torques
Power terminals
Motor size [kW]
Thread size
Up to 7.5 kW
11-22 kW
Relay, M2.5:
0.5 Nm.
Input control, M2: 0.2 Nm.
25.1.3 Line reactors
Max line reactor size must not exceed 2 mH.
25.1.4 Fuse size/circuit breaker
If a short circuit happens the pump can be used on a mains sup-
ply delivering not more than 5000 RMS symmetrical amperes,
600 V maximum.
Fuses
When the pump is protected by fuses they must be rated for
480 V. Maximum sizes are stated in table below.
Motors up to and including 7.5 kW require class K5 UL-listed fuses.
Any UL-listed fuse can be used for motors from 11 to 22 kW.
Circuit breaker
When the pump is protected by a circuit breaker this must be
rated for a maximum voltage of 480 V. The circuit breaker must
be of the "Inverse time" type.
The interrupting rating (RMS symmetrical amperes) must not be
less than the values stated in table below.
USA - hp
2-pole
4-pole
Fuse size
1
1
25 A
1.5
1.5
25 A
2
2
25 A
3
3
25 A
5
5
40 A
7.5
-
40 A
10
7.5
50 A
15
15
80 A
20
20
110 A
25
25
125 A
30
-
150 A
36
Torque [Nm]
M4
2.35
Min. 2.2
M4
Max. 2.8
Circuit breaker type/model
25 A / Inverse time
25 A / Inverse time
25 A / Inverse time
25 A / Inverse time
40 A / Inverse time
40 A / Inverse time
50 A / Inverse time
80 A / Inverse time
110 A / Inverse time
125 A / Inverse time
150 A / Inverse time
Europe - kW
2-pole
4-pole
Fuse size
-
0.55
25 A
0.75
0.75
25 A
1.1
1.1
25 A
1.5
1.5
25 A
2.2
2.2
25 A
3
3
25 A
4
4
40 A
5.5
-
40 A
7.5
5.5
50 A
11
11
80 A
15
15
110 A
18.5
18.5
125 A
22
-
150 A
25.1.5 Overload protection
Degree of overload protection provided internally by the drive,
in percent of full-load current: 102 %.

25.2 General considerations

For installation in humid environment and fluctuating temperatures,
it is recommended to keep the pump connected to the power sup-
ply continuously. This will prevent moisture and condensation
build-up in the terminal box.
Start and stop must be done via the start/stop digital input (termi-
nal 2-3).
Nous nous réservons tout droit de modifications.
1
Circuit breaker type/model
25 A / Inverse time
25 A / Inverse time
25 A / Inverse time
25 A / Inverse time
25 A / Inverse time
25 A / Inverse time
40 A / Inverse time
40 A / Inverse time
50 A / Inverse time
80 A / Inverse time
110 A / Inverse time
125 A / Inverse time
150 A / Inverse time

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Tped 2000 sérieTped 2000 serie

Table des Matières