9. Setting example

Monitoring of limit values and differential pressure

(see also principle comparator mode, page 25)
Application
Monitoring of a filter system by recording the measured pressure values before and behind the filter.
System requirements
Max. possible system pressure
Operating pressure (nominal pressure)
Min. permissible operating pressure
Measuring range of the sensors/transmitters
Analogue output of the sensors/transmitters
The measuring ranges and output signals
of the sensors/transmitters have to be identical!
Monitor parameters
MOD
Mode
INx
Input (type)
DHI
Display High
DLO
Display Low
FO1
Function Output 1
FO2
Function Output 2
SP1
Switch point Output 1
SP2
Switch point Output 2
HY1/2
Hysteresis for SP1/2
AO3
Analogue Output 3 (type)
AE3
Analogue End Output 3
AS3
Analogue Start Output 3
Output characteristics (OUT1...3)
38
Example values
0...25 bar
4...20 mA
Setting (value)
= measured value A (e.g. constant)
= measured value B (e.g. variable)
21 bar
20 bar
5 bar
Description
A-B
Differential monitoring [∆ bar]
4-20
Analogue outputs of the sensors/transmitters
25
Max. measured value of the sensor/transmitter
0
Min. measured value of the sensor/transmitter
(4)
Relay 1 de-energises when current value is above SP1
(switches back at SP1 – HY1)
(4)
Relay 2 de-energises when current value is above SP1
(switches back at SP2 – HY2)
Differential pressure ∆ bar 1 (limit value 1)
5
Differential pressure ∆ bar 2 (limit value 2)
15
10
Reset point [% of SPx]
0...20 mA signal for ∆ bar evaluation
0-20
21
Max. possible differential pressure (∆ bar
0
Min. possible differential pressure (∆ bar
filter system
)
max
)
min