ZS 80
//
Montage- und Anschlussanleitung / Seilzug-Notschalter
Mounting and wiring instructions / Emergency pull-wire switch
Instructions de montage et de câblage / Arrêt d'urgence à commande par câble
Istruzioni di montaggio e collegamento / Interruttore di emergenza a fune
Instruções de montagem e instalação / Chave de emergência acionada por cabo
Инструкция по монтажу и подключению / Аварийный тросовый выключатель
English
Use of the mounting and wiring instructions
Target group: authorised and qualified staff.
All actions described in these instructions may only be performed by
qualified persons who have been trained and authorised by the
operating company.
1. Read and understand these mounting and wiring instructions.
2. Comply with the valid occupational safety and accident prevention
regulations.
3. Install and operate the device.
Selection and installation of devices and their integration in control
systems demand qualified knowledge of all the relevant laws, as well
as the normative requirements of the machine manufacturer.
In case of doubt, the German language version of these instructions
shall prevail.
Scope of delivery
1 device, 1 mounting and wiring instructions, carton.
Intended use
The device is applied on machines and plants where an emergen-
cy-stop command is required along the complete pull-wire. Pulling
or breaking of the prestressed wire triggers the switching function of
the emergency pull-wire switch and thus lead to contact latching. The
reset can only be carried out manually by unlocking with the
push-button.
Mounting and wiring
Before mounting the pull-wire, remove the red PVC sheath from the
the pull-wire in the clamping range of the pull-wire! After fitting the
wire, pull strongly on it several times, as the pull-wire and the wire
thimble will deform. Subsequently, retense the wire using the DUPLEX
wire clamp, eye-bolt or tensioner.
N.B.
Any mounting position is possible. Reconstruction and alterations to
the device which might affect the safety function are not allowed. The
device has been developed in order to assure safety functions as a
part of an entire plant or machine. A complete safety system normally
covers sensors, monitoring modules, indicator switches and concepts
for safe disconnection. For the integration of the device in the entire
system: strictly observe and respect the control category determined
in the risk assessment. Therefore, a validation according to EN ISO
13849-2 or EN 62061 is necessary. Furthermore, the Performance
Level according to EN ISO 13849-1 and SIL CL Level according to EN
62061 can be lower than the single level because of the combination
of several safety components and other safety-related devices, e.g.
by serial connection of sensors. It is the responsibility of the manufac-
turer of a plant or machine to guarantee the correct general function.
Subject to technical modifications. steute does not assume any liability
for recommendations made or implied by this description. New claims
for guarantee, warranty or liability cannot be derived from this docu-
ment beyond the general terms and conditions of delivery.
Maintenance
With careful mounting as described above, only minor maintenance is
necessary. We recommend a routine maintenance as follows:
1. Check pull-wire function.
2. Remove all dirt.
3. Check sealing of the cable or conduit connections.
Cleaning
- In case of damp cleaning: use water or mild, non-scratching,
non-chafing cleaners.
- Do not use aggressive cleaners or solvents.
Disposal
- Observe national, local and legal regulations concerning disposal.
- Recycle each material separately.
Mounting and set-up
In order to function correctly, the ZS 80 emergency pull-wire switch
must be set up in the middle position with a pretensioned pull wire. In
this middle position the pointer position should correspond to Fig. 1.
In the middle position with a pretensioned pull wire, the NC contacts,
e.g. 11-12, are closed and the NO contacts, e.g. 23-24, are open. The
switch can only be released in this middle, pretensioned position.
Fig. 1
Switching function
When the wire is pulled, or if the wire breaks, the NC contacts, e.g.
11-12, are opened and the NO contacts, e.g. 23-24, are closed and then
locked in this position. The switch can only be released using the blue
release lever.
2 / 16
I Release
0 Latching
Middle position
Fig. 2