PTB 03 ATEX 1030 X
Technicaldata/Safeoperation
6.3.5. Type of explosion protection
The composition of the explosion protection code follows the explosion
protection types of the components used in each case:
Solenoid with or without
II 2 G Ex d e IIC T4 resp. T5
terminal box
II 2 D Ex tD A21 IP 65 T135 °C resp.
T100 °C
Solenoid with terminal
II 2 G Ex d e mb IIC T4
box and fuse
II 2 D Ex tD A21 IP65 T135 °C
Solenoid without terminal
II 2 G Ex d e ia IIC T4 resp. T5
box with proximity switch
II 2 D Ex tD A21 IP65 T135 °C resp.
T100 °C
Solenoid with terminal
II 2 G Ex d e ia mb IIC T4
box, fuse and proximity
II 2 D Ex tD A21 IP65 T135 °C
switch
6.4. general Technical data
6.4.1. electrical data
Type
77. - ... - ... - .
Temperature class
T4
Type of current
Universal
rated voltage
24 ... 240 V
Voltage tolerance
+10 % / -10 %
rated current
0,085 ... 0,014 A
pick-up current
01,66 ... 0,166 A
pick-up power
40 W
power consumption for
3 W
holding in equilibrium
max. number of
20 / min
switching actuations ca
6.4.2. electrical connection
Version
code
PD30*
* Permanently installed rubber sheathed
cable of Type H05 RN-F3G0.75
english
78. - ... - ... - .
T5
Universal
24 ... 240 V
+10 % / -10 %
0,085 ... 0,014 A
01,66 ... 0,166 A
40 W
3W
10 / min
execution
internal
****JWxx
code
11