Operation Of The Instrument; Set Alarm Limits - Hydrotechnik SEG 1060 Mode D'emploi

Afficheur encastrable multifonction
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SEG 1060
Instructions for use
12.
13.
for the set time before an alarm is triggered.
14.
15.
16.
– leave configuration menu.
5

Operation of the instrument

The following operational actions are described here:
x
set switch points
x

set alarm limits

x
read and delete min-/max-value buffer
x
read alarm indications
x
meanings of error codes
5.1
Set switch points of output function 2-point regulator
When the output function „2-point regulator" is set (see section 4.6), you
do not need to enter the configuration to set the switch points:
1.
> 2 seconds –
2.
3.
4.
5.
6.
7.
– leave configuration menu.
Application example
You have a heater plate and want to regulate it to a temperature of +120°
C with a hysteresis of ±2° C. You have to set:
= 120 (°C) /
5.2
Set alarm limits of output function alarm
When the output function „Alarm" is set (see section 4.6), you do not need
to enter the configuration to set the alarm limits:
1.
> 2 seconds –
2.
3.
4.
20
.
set value of alarm delay in seconds; the alarm case must exist
.
.
.
set value, when regulator shall switch on.
.
.
set value, when regulator shall switch off.
.
= 122 (°C)
.
set value when max-alarm shall be triggered
.
.
Version 1.2