7 Output settings

7.1 Switching outputs

The HNS 526 has either 1 or 2 switching outputs. The following settings can be made under
the basic settings:

7.1.1 Switch point setting (SP)

One switch point and one switch-back point can be set for each switching output. The
particular output will switch when the pre-set switch point is reached and then switch back
when the level drops below the switch-back point.
E
Example for switch point 1 (N/C and N/O function):
Normally open function
Normally closed function
Abbreviations:
Note:
It is only possible to set the switch point (SP) if it is higher than the respective
switch-back point (RP). In the case of low SPs we recommend setting the RP first.
Version: 06.10.2014
Level
On
Off
On
Off
"SP1", "SP2"
= switch point 1 / switch point 2
"RP1", "RP2"
= switch-back point 1 / switch-back point 2
"HNO",
= N/O when hysteresis function is active
"HNC"
= N/C when hysteresis function is active