HNS 526
7.1.2 Window function setting (Fno / Fnc))
The window function enables a range to be monitored. An upper and a lower switch point
which defines the range can be assigned to each switching output.
The relevant output will then switch when the level enters this range.
When the level leaves this range, i.e. when the switch-back point has been reached, the
output switches back. The lower switch-back value is just below the lower switch value. The
upper switch-back value is just above the upper switch value. The range between the switch
value and the switch-back value forms a safety margin which prevents unwanted switching
operations from being triggered (such as those triggered by the pulsations of a pump).
Example for switching output 1 (N/C and N/O function):
Level
FH1 plus 1 %FS
FH1
FH1
FL1
FL1
FL1 minus 1 %FS
FNO
FNO
Ein
Ein
On
Normally open function
Schließerfunktion
Aus
Aus
Off
FNC
FNC
Ein
Ein
On
Normally closed function
Öffnerfunktion
Off
Aus
Aus
Abbreviations:
"FH1", "FH2"
"FL1", "FL2"
"FNO"
"FNC"
Notes:
■ It is only possible to set the switch point (SP) if it is higher than the respective
switch-back point (RP). In the case of low SPs we recommend setting the RP first.
■ The window function only works properly (switching on and off) if all switch values
(including the safety margin) are higher than the blind zone and below the
maximum scanning range.
Version: 06.10.2014
Off
Aus
Aus
Sicherheitszone
Sicherheitszone
Safety zone
On
Ein
Ein
Sicherheitszone
Sicherheitszone
Safety zone
= upper switch value 1 / upper switch value 2
= lower switch value 1 / lower switch value 2
= N/O when window function is active
= N/C when window function is active
HYDAC ELECTRONIC GMBH
Reverse switch point
Rückschaltwert
Schaltwert
Switch point
Schaltwert
Ein
Ein
On
Switch point
Schaltwert
Schaltwert
Reverse switch point
Rückschaltwert
Aus
Aus
Off
t
t
13
E
Part No.: 669869