Technical Specifications - AKO PROPlus 3PH BASIC Guide Rapide

Masquer les pouces Voir aussi pour PROPlus 3PH BASIC:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1569H051 Ed.01

10.- Technical specifications

Rated voltage Un...........................................................................................................400 V~ ±10 % 50 Hz ±5 %
Rated voltage Ue...........................................................................................................230 V~ ±10 % 50 Hz ±5 %
ALARM relay ........................................................................................................................... 8A at 250V, cosj=1
Probe temperature range...........................................................................................................–45.0 ºC to 99.9 ºC
Resolution, setting and differential ................................................................................................................0.1 ºC
Thermometric precision.................................................................................................................................± 1 ºC
Precision of the NTC probe at 25 ºC .............................................................................................................± 0.4 ºC
Input for NTC probe .............................................................................................................................AKO-14901
Maximum input power in the operation ..........................................................................................................30 VA
Working ambient temperature............................................................................................................-5 ºC to 40 ºC
Storage ambient temperature ..........................................................................................................–30 ºC to 70 ºC
Overvoltage category .....................................................................................................................II s/ EN 61439-1
Degree of pollution ........................................................................................................................II s/ EN 61439-1
Degree of protection .......................................................................................................................................IP65
Dimensions .............................................................................................................400(An) x 300(Al) x 135(P) mm
Double isolation between power supply, secondary circuit and relay output.
Type of assembly................................................................................................................................Fixed internal
Internal buzzer
Encapsulated assembly