7.- Basic configuration
The basic configuration menu allows the equipment to be configured for the most common applications. Press the
SET key for 5 seconds to access it.
If the access code is activated, a 2 digit code is requested, if the code entered is not correct the unit will not enter
programming.
If more specific configuration is required use the
After 20 seconds without touching any key, the unit returns to the previous level without saving changes or it will
exit programming.
Function of the keys in programming
Passes on to the next parameter or increases the
SET
value of the parameter.
Accesses the selected parameter or accepts the
SET
value.
SP: Set point
It defines the temperature that should be inside the cold storage room:
Minimum: –45.0 *
Ÿ
Maximum: 99 *
Ÿ
*(Depends on the bottom/top locking of the set point).
d0: Defrost frequency
Time that must elapse between the starting of each defrost.
d1: Maximum defrost duration
The defrost will end after this time has elapsed since it started.
F3: Fan status during defrost
It defines the status of the fans during defrost.
A1: Maximum alarm probe 1
Defines the temperature at which the maximum alarm will be triggered. Only affects probe 1.
Minimum: –45.0 *
Ÿ
Maximum: 99 *
Ÿ
*(Depends on the bottom/top locking of the set point).
A2: Minimum alarm probe 1
Defines the temperature at which the minimum alarm will be triggered. Only affects probe 1.
Minimum: –45.0 *
Ÿ
Maximum: 99 *
Ÿ
*(Depends on the bottom/top locking of the set point).
advanced configuration menu (See user manual on www.ako.com
Passes back to the previous parameter or
SET
decreases the value of the parameter.
Allows exiting a parameter without saving the
ESC
changes or exiting programming.
0= OFF
1= ON
21
1569H051 Ed.01
)