Operation
IMPORTANT: After connecting the key to the equipment wait for 5 seconds
before starting the reading or writing process.
RECORD key
Write the data contained in the key memory to the controller.
Keep the key pressed until the COM led starts flashing quickly.
When recording is complete the controller will reset.
READ key
It reads the data from the controller and stores them in the programming key.
Keep the key pressed until the COM led starts flashing quickly.
When recording is complete the controller will reset.
LED ON
Steady or flashing: Indicates that the key is connected to the controller.
LED COM
Steady: Indicates an error in the transmission/reception of data
Fast flashing: Indicates transmission/reception of data in progress. At the end of the
transmission LED COM will switch off.
Slow flashing: Indicates compatibility error- the data contained in the memory of the key
is not compatible with the model of controller connected. Data can only be read from the
controller to the key.
NOTE: To restart after a transmission or compatibility error, turn off the power
supply or disconnect the controller connector cable.
IMPORTANT: Never disconnect the programming key during data transmission.

Technical specifications

Length of cable from programming key to controller . . . . . . . . . . . . . . . . . . . . 300 mm
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Vdc nominal
Supply current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-80018 / 500 mA máx.
Environmental specifications:
Ambient working temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0ºC to 50ºC
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30ºC to 70ºC