6.1 Technical data

Symbols
Symbols
Meaning
X
Measured variable
X0
Lower limit of the measured variable
X1
Break point of the measured variable
X2
Upper limit of the measured variable
Y
Output variable
Y0
Lower limit of the output variable
Y1
Break point of the output variable
Y2
Upper limit of the output variable
U
Input voltage
Ur
Rated value of the input voltage
U 12
Phase-to-phase voltage
L1 – L2
U 23
Phase-to-phase voltage
L2 – L3
U 31
Phase-to-phase voltage
L3 – L1
U1N
Phase-to-neutral voltage
L1 – N
U2N
Phase-to-neutral voltage
L2 – N
U3N
Phase-to-neutral voltage
L3 – N
UM
Average value of the voltages
(U1N + U2N + U3N) / 3
I
Input current
I1
AC current L1
I2
AC current L2
I3
AC current L3
Ir
Rated value of the input current
IM
Average value of the currents (I1 + I2 + I3)/3
IMS
Average value of the currents and sign of the
active power (P)
IB
RMS value of the current with wire setting
range (bimetal measuring function)
IBT
Response time for IB
BS
Slave pointer function for the measurement
of the RMS value IB
BST
Response time for BS
ϕ
Phase-shift between current and voltage
F
Frequency of the input variable
Fn
Rated frequency
P
Active power of the system
P = P1 + P2 + P3
P1
Active power phase 1
(phase-to-neutral L1 – N)
P2
Active power phase 2
(phase-to-neutral L2 – N)
P3
Active power phase 3
(phase-to-neutral L3 – N)
Q
Reactive power of the system
Q = Q1 + Q2 + Q3
Q1
Reactive power phase 1
(phase-to-neutral L1 – N)
30
Symbols
Meaning
Q2
Reactive power phase 2
(phase-to-neutral L2 – N)
Q3
Reactive power phase 3
(phase-to-neutral L3 – N)
S
Apparent power of the system:
2
2
S = √ I
+ I
1
2
S1
Apparent power phase 1
(phase-to-neutral L1 – N)
S2
Apparent power phase 2
(phase-to-neutral L2 – N)
S3
Apparent power phase 3
(phase-to-neutral L3 – N)
Sr
Rated value of the apparent power of the
system
PF
Active power factor cosϕ = P/S
PF1
Active power factor phase 1
PF2
Active power factor phase 2
PF3
Active power factor phase 3
Reactive power factor sin ϕ = Q/S
QF
QF1
Reactive power factor phase 1
QF2
Reactive power factor phase 2
QF3
Reactive power factor phase 3
LF
Power factor of the system
LF = sgnQ · (1 – | PF | )
LF1
Power factor phase 1
sgnQ1 · (1 – | PF1 | )
LF2
Power factor phase 2
sgnQ2 · (1 – | PF2 | )
LF3
Power factor phase 3
sgnQ3 · (1 – | PF3 | )
c
Factor for the intrinsic error
R
Output load
Rn
Rated burden
H
Power supply
Hn
Rated value of the power supply
CT
c.t. ratio
VT
v.t. ratio
Input
Waveform:
Sinusoidal
Nominal frequency:
50, 60 or 16 2/3 Hz
Consumption [VA]
(at external
power supply):
Voltage circuit: U
Current circuit: ≤ I
2
2
2
2
+ I
· √ U
+ U
+ U
3
1
2
3
P1/S1
P2/S2
P3/S3
Q1/S1
Q2/S2
Q3/S3
2
/ 400 kΩ
2
· 0.01 Ω