Using the Programming Menus
Main Menu Options List
enter to confirm, or use the arrow keys to scroll to No to
Press
cancel. The screen displays the concentration during calibration.
A success or failure message displays and the screen returns to the
main menu option.

TestMode Menu

The TestMode menu performs a test of all functions on the unit. All
outputs are activated according to their failsafe mode, relay setting, and
buzzer setting. All functions are activated simultaneously for a maximum
of 3 minutes, or until the user cancels the test. The unit does not
detect gas during this TestMode procedure. Press enter to access the
TestMode.
Use the arrow keys to scroll to
begin the test sequence
To cancel the test, press
22
Set Span
198 ppm
* Menu *
TestMode
Yes or No and press any key to
TestMode
Yes
enter at anytime when Stop displays.
TestMode
Stop
E
Point Network Gas Monitor User Manual