Specifications
Sensor Overload
Detection Ranges and Alarm Levels
Gas Detected
CO
Carbon monoxide
H
S
Hydrogen sulfide
2
NO
Nitrogen dioxide
2
O
Oxygen
2
COMB
Combustibles
Maximum Overload is the cell exposure to gas concentration that may
result in permanent damage to the cell.
Sensor Overload
•
Sensor overload occurs whenever the gas concentration reading
is higher than the full scale value, no matter how high the gas
concentration is.
•
Overload Warning state is latched when true. It stays activated
indefinitely and is independent of gas concentration reading.
•
To unlatch Overload Warning, hold
8 seconds.
•
When Overload Warning is set and the buzzer is deactivated,
the buzzer will beep for 1 second every 10 minutes.
•
The LCD displays
set.
•
On network units like 301C systems, the Overload Warning
states for the E
when on a BACnet building automation system. Overload
warning states are available through the reliability property of
the sensor analog input object (AI0).
•
The LED blinks twice per second during overload, and once per
second under normal conditions.
28
Range
Alarm A
0-250 ppm
25 ppm
0-50 ppm
10 ppm
0-10 ppm
0.7 ppm
0-25 %vol
19.5 %vol.
0-100 %LEL
25 %LEL
OVERLOAD whenever Overload Warning is
Point are available through warning flag #Z
3
Alarm B
Alarm C
200 ppm
225 ppm
15 ppm
20 ppm
2 ppm
9 ppm
22 %vol.
22.5 %vol
50 %LEL
90 %LEL
ESC for at least
E
Point Network Gas Monitor User Manual
3
Maximum
Overload
500 ppm
150 ppm
1000 ppm
100 %vol
100 %LEL