Les langues disponibles

IAQ :
Intake air quality sensor (option)
OAH :
Outdoor air hygrometry sensor (option)
SD :
Smoke detector (option)
ECM :
Economiser dampers motor (option)
HWV :
Hot water coil modulating valve (option)
HWC :
Anti-freezing, hot water battery warning
DFA :
Clogged filter warning (DP>250Pa)
AF :
Air pressostat (DP<50Pa)
ON/OFF :
ON/OFF switch (not supplied)
SWS :
Winter/Summer switch (not supplied)
KM1/2 :
C1/2 compressors power contactor
KM3/4/7/8 :
Fan power contactors
KM13 :
Relais de commande des ventilateurs plug-fan
K5/6 :
Heating elements power contactors (option)
EV1/2 :
Circuits 1 and 2 cycle inversion valve (option)
KA2/3 :
Relay contactors of the outdoor fan (option "all seasons"/ heat pump mode)
RANGE AND SETTINGS OF THEMAL PROTECTION / NOMINAL INTENSITY OF THE
CONTACTORS (CLASSE AC3)
RT30
Model
PE
Q1
Range
13-18A
Adjustment
13A
Q2
Range
13-18A
Adjustment
13A
Q3
Range
2.5-4A
Adjustment
3.2A
Q4
6A
Q7/8
Range
/
Adjustment
/
FT1
10A
FT3
/
FT4
/
Contactor AC3
KM1
18A
KM2
18A
KM3
9A
KM4
9A
KM7
9A
KM8
/
RT40
GE
PE
GE
13-18A
15A
13-18A
15A
4-6.3A
2.5-4A
6-10A
4.6A
3.2A
8.3A
6A
/
/
10A
/
/
18A
18A
9A
12A
9A
9A
/
15
RT50
PE
GE
PE
17-23A
19.5A
17-23A
19.5A
4-6.3A
9-14A
4.6A
11A
6A
/
/
10A
/
/
25A
25A
9A
12A
9A
9A
/
RT60
GE
20-25A
21A
20-25A
21A
9-14A
11A
6A
/
/
2A
10A
10A
25A
25A
12A
9A
9A
9A