Installation Instructions Mata; Preparation; The Chimney Flue; Fire Safety - WANDERS Mata Mode D'emploi Et Instructions D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation Instructions Mata

The Mata is tested in accordance with the international EN 13240 standardization, and has an extra additional standardization
for optimally environment-friendly heating devices related to flue gases (Section 15a B-Vg. Des BmfWA). The stove can be
connected to a flue tube to which several stoves are connected. The flue tube has a diameter of 150 millimetres.
The heating device must be placed by an acknowledged installer and according to the installation instructions
given below. The national and local rules and regulations for placing and using wood-burning stoves are
equally applicable. WANDERS does not give any guarantee if the Mata is connected or installed incompletely or
incorrectly.
It is not allowed to place the stove in:
Arcades and corridors accessible to the public.
Stairwells, except in buildings with no more than 2 dwellings.
Spaces where highly flammable or explosive materials are used.
Spaces where an exhaust system is used or where a mechanical exhaust system is placed, except when the air supply is
taken directly from outside to assure a hazardless combustion.

Preparation

The chimney flue

Before placing the stove you must observe the following points:
If the stove is connected to an existing chimney, you must first have the chimney professionally cleaned and checked by
a qualified chimney sweep company. Any cut-off valves or stop valves must be removed.
The flue tube of the stove must be connected with the chimney without diversions.
The underpressure in the chimney must be
at least 12 Pa or 0.12 mbar.
The chimney flue must always end up in
outlet area 1 (see the drawing)
At the time of placing the stove, the chim-
ney flue must be clean, leak-proof and with-
out obstructions, and must have a diameter
of 150 mm.
Any bends in the flue tube must not exceed
45 degrees.
Ensure that the chimney tube can discharge
the flue gases adequately, properly and
safely.

Fire Safety

For reasons of fire safety is it important to observe the instructions below before installing the stove.
1.
If the floor around the stove is made of combustible material, you must use a floor slab. The floor slab must measure at
least: - 50 cm from the stove on the front side of the door - 30 cm from the stove on the sides of the door.
2.
Keep at least a distance of 80 cm between the stove and combustible objects such as curtains, wooden objects
(cupboards and paintings) and glass objects. Keep the same distance from the flue tube.
3.
Wooden construction parts within the radiation range of the stove (80 cm from the exterior of the stove) must be covered
with fireproof material.
4.
If the flue tube goes through a ceiling and/or roof that consist of flammable materials, the ceiling and the roof must be
covered with fireproof materials all around (about 80 cm). Pay also attention to joisted floor layers and any electric wiring.
5.
Keep a distance of at least 50 cm (in all directions) between the stove and supporting steel construction parts.
6.
Shield off all combustible materials within a radius of 100 cm from the stove openings with non-combustible materials.
7.
Never cover the chimney breast with combustible material (e.g. paper covering).
8.
The wall behind the stove must consist of, or be insulated with, fire-proof materials. The insulation material must resist a
1
3
3
A X
X > 23˚
1
X
500 mm
X < 23˚
GB
3
21

Publicité

Table des Matières
loading

Table des Matières