• The installation of both anti-derailment buffers is absolutely obligatory before starting programming.
• Make sure the safety devices are at rest and the ECU is receiving mains power otherwise you will not be able to enter programming.
• The system automatically sets itself to work with one or two gate leaves.
Caution: If the symbol
minutes has passed since the programmer was powered
up, the gate will start moving automatically (after the warn-
ing lights have flashed for 10 seconds) to the completely
closed position (automatic repositioning).
Dip-switch settings DS1
CAUTION:
If you change the dip settings you must memorise them; press the
"PROG" button, "dIP" will appear on the display indicating that the settings
have been memorised.
Sequential command TD/CH1
Dip 1 "ON" = Sequential command "open-close"
Travel direction inversion only during closing.
Dip 1 "OFF" = Sequential command "open-block-close-block"
Automatic reclosing (DIP 2)
Dip 2 "ON" = Automatic reclosing enabled
Dip 2 "OFF" = Automatic reclosing disabled
Pre-flashing (DIP 3)
Dip 3 "ON" = Pre-flashing activated
Dip 3 "OFF" = Pre-flashing excluded
Warning light output (DIP 4)
Dip 4 "ON" = Warning light output intermittent
Dip 4 "OFF" = Warning light output fixed
Indicator light (DIP 5)
Dip 5 "ON" = Indicator light intermittent
Dip 5 "OFF" = Indicator light fixed
*
The indicator light flashes slowly during opening, rapidly during closing;
remains lit when the gate is blocked but not completely closed and is off when
the gate is completely closed.
FTCI mode (DIP 6)
Dip 6 "ON" = FTCI also active when the gate is blocked
If the photocells are in alarm and the gate is blocked, no movement commands
will be accepted (even opening commands).
Dip 6 "OFF" = FTCI active only during closing
In both cases activating the FTCI safety device during the closing stage will
force travel direction inversion.
FTCI test (DIP 7)
Dip 7 "ON" = FTCI test enabled
Dip 7 "OFF" = FTCI test disabled
If you enable the security test you will have to connect both the transmitter and
the receiver to the controlled load output (CTRL 30 vdc). When the test is enabled
one second will pass between receiving a command and carrying it out.
FTCS test (DIP 8)
Dip 8 "ON" = FTCS test enabled
Dip 8 "OFF" = FTCS test disabled
If you enable the security test you will have to connect both the transmitter and
the receiver to the controlled load output (CTRL 30 vdc). When the test is enabled
one second will pass between receiving a command and carrying it out.
Opening direction gate delay (DIP 9)
Dip 9 "ON" = Opening direction gate delay enabled
Dip 9 "OFF" = Opening direction gate delay disabled
If you enable gate delay the following will occur: during the opening movement
gate leaf 1 moves first and then gate leaf 2. In the closing direction gate leaf
2
moves first then gate leaf 1. If gate delay is disabled both gate leaves move
simultaneously.
PROGRAMMING PROCEDURE (Setting the programmer and the current sensor)
appears on the display after 3
*
Electric lock (DIP 10)
Dip 10 "ON" = Electric lock enabled
Dip 10 "OFF" = Electric lock disabled
If the electric lock is enabled the ELS output (binding post 8) will be activated
before gate leaf 1 moves and will remain active until gate leaf one has moved
a few centimetres.
CURRENT SENSOR
The programmer checks the electrical input to the motor, detecting
any eventual increase in effort above the normal operating limits and
intervenes as an additional safety device. When the sensor intervenes
the gate automatically inverts the travel direction.
20