Motor Connection - Lenze E82MV Série Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4
Mechanical installation
Wall mounting

Motor connection

4.2.3
Motor connection
{
Danger!
ƒ
ƒ
8200mot468
PES
X2/PE2
X2/BR1, X2/BR2
X2/T1, X2/T2
Cable cross−sections U, V, W, PE
Type
E82MV302_4B
E82MV402_4B
E82MV552_4B
E82MV752_4B
84
All control terminals only have basic insulation (single isolating distance)
after connecting a PTC thermistor or a thermal contact.
Protection against accidental contact in case of a defective isolating
distance is only guaranteed through external measures, e. g. double
insulation.
Use low−capacitance motor cables!
(core/core £ 75 pF/m, core/shield £ 150 pF/m)
The shortest possible motor cables have a positive effect on the drive behaviour!
HF−shield termination by large surface connection to PE
Do not use the terminal
Brake resistor terminals
(For information on operation with brake resistor: see operating instructions)
Terminals of motor temperature monitoring with PTC thermistor (PTC) or thermal
contact
Activate motor temperature monitoring with C0119 (e.g. C0119 = 1)!
Cable cross−sections U, V, W, PE
2
[mm
]
1
1.5
2.5
4
l
[AWG]
18
16
14
12
91
EDK82MV752 DE/EN/FR 7.2