Flow switch installation
4
Flow switch installation
CAUTION! Material damage!
When soldering the copper pipe fitting ( § 4.2) or the threaded nipple ( § 4.3) , the
flow switch (body with paddle mechanism) and the O-ring must be dismounted. Over-
heating during soldering will damage these components and impair their operation.
Remove the flow switch and the O-ring before you start soldering.
4.1 General installation instructions
When choosing the installation site, ensure that the specified limit values (( § 9
"Technical data") are not exceeded.
Select suitable measures to prevent the medium from freezing.
If the flow switch is to be used in ambient temperatures of <4°C, do not carry out any op-
eration beforehand with pure water, e.g. a test run. Residual water in the flow switch can
result in frost damage.
Firstly, clean the pipe system in which the flow switch is to be installed and remove any
magnetic particles, e.g. welding residue.
The straight in- and outlet pipe (in front of and behind the flow switch) has to be at least 5
x DN.
The nominal installation position of the flow switch is an "upright standing position" in
horizontal pipework.
The switches should only be installed in a vertical position,
deviation max. 45° ( Fig. 1).
Please contact the manufacturer if other installation positions
are desired.
Please make sure that there are no external magnetic fields
in the immediate vicinity of the flow switch, since these can
impair device functioning ( Fig. 2a).
There is an arrow on the flow switch. Ensure that this arrow
is parallel with the pipe shaft and is facing in the direction of
flow during installation ( Fig. 2a).
The brass and stainless steel union nuts ¾"BSP (version
VH...) have a tightening torque of 25...30 Nm.
When tightening the union nuts, hold the pipe section against
the surface provided ( Fig. 2b).
The plastic union nuts (version VK...) have a tightening torque
of 7...8 Nm.
Additional information for flow switch version VH...X
Please observe the specified limit values when choosing the installation site ( § 9
"Technical data").