INDOOR UNIT WIRING
1. Prepare the cable for connection
a. Using wire strippers, strip the rubber jacket
from both ends of the signal cable to reveal
about 5.9in (150mm) of the wire.
b. Strip the insulation from the ends of the
wires.
c. Using a wire crimper, crimp the u-lugs to
the ends of the wires.
2. Open the front panel of the indoor unit. Using
a screwdriver, remove the cover of the electric
control box on your indoor unit.
3. Thread the power cable and the signal cable
through the wire outlet.
©2024 Innovair Solutions. All Rights Reserved.
4. Connect the u-lugs to the terminals.
Match the wire colors/labels with the labels on
the terminal block. Firmly screw the u-lug of
each wire to its corresponding terminal. Refer
to the Serial Number and Wiring Diagram
located on the cover of the electric control box.
CAUTION
While connecting the wires, please strictly
•
follow the wiring diagram.
The refrigerant circuit can become very hot.
•
Keep the interconnection cable away from the
copper tube.
5. Clamp down the cable with the cable clamp. The
cable must not be loose or pull on the u-lugs.
6. Reattach the electric box cover.
29
www.innovair.com