Anchor Outdoor Unit
3
WARNING
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIME.
The outdoor unit can be anchored to the ground or to a wall-mounted bracket with bolt(M10). Prepare
the installation base of the unit according to the dimensions below.
Prepare the installation base of the unit according to the dimensions below.
Outdoor Unit Types and Speci cations (Split Type Outdoor Unit)
Air inlet
Outdoor Unit Dimensions
W x H x D
30.1inx21.8inx11.9in
(765mmx555mmx303mm)
31.7inx21.8inx12.9in
(805mmx554mmx330mm)
35.0inx26.5inx13.5in
(890mmx673mmx342mm)
©2024 Innovair Solutions. All Rights Reserved.
A
Air inlet
Air outlet
Top view
Mounting Dimensions
Distance A
Distance B
17.8 in
11.3 in
(452mm)
(286mm)
12.5 in
20.1 in
(317mm)
(511mm)
26.1 in
13.9 in
(663mm)
(354mm)
Front view
Rows of series installation
The relations between H, A and L are as follows.
L
L ≤ 1/2H
L ≤ H
1/2H < L ≤ H
L > H
Cannot be installed
H
NOTE
H: Unit height
L: Height of the wall behind the unit
A: Distance between unit and wall
20
H
W
A
9.8in (25cm) or more
11.8in (30cm) or more
www.innovair.com
L