Anchor Outdoor Unit
3
WARNING
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIME.
The outdoor unit can be anchored to the ground or to a wall-mounted bracket with bolt(M10). Prepare
●
the installation base of the unit according to the dimensions below.
●
Prepare the installation base of the unit according to the dimensions below.
Outdoor Unit Types and Speci cations (Split Type Outdoor Unit)
Air inlet
Outdoor Unit Dimensions
W x H x D
30.1inx21.8inx11.9in
(765mmx555mmx303mm)
31.7inx21.8inx12.9in
(805mmx554mmx330mm)
35.0inx26.5inx13.5in
(890mmx673mmx342mm)
©2024 Innovair Solutions. All Rights Reserved.
A
Air inlet
Air outlet
Top view
Mounting Dimensions
Distance A
Distance B
17.8 in
11.3 in
(452mm)
(286mm)
12.5 in
20.1 in
(317mm)
(511mm)
26.1 in
13.9 in
(663mm)
(354mm)
Front view
Rows of series installation
The relations between H, A and L are as follows.
L
L ≤ 1/2H
L ≤ H
1/2H < L ≤ H
L > H
Cannot be installed
H
NOTE
H: Unit height
L: Height of the wall behind the unit
A: Distance between unit and wall
20
H
W
A
9.8in (25cm) or more
11.8in (30cm) or more
www.innovair.com
L