34
11.5
ALTERNATE CONDENSATE DRAIN PIPING INSTALLATION USING 1/2" PVC OR 3/4"
CPVC
1. Install the condensate trap according to instructions included in this manual. 1/2" and 5/8" rubber hoses
shown are pre-installed inside the furnace from factory.
IOM
IOM
FIGURE 23
2. If installing with 1/2" PVC, use the 1/2" hose. If installing with 3/4" CPVC, use the 5/8" hose. Slide the
appropriate hose over the condensate trap outlet and cut it fl ush with the end of the outlet. The remaining
rubber should be fl ush with the end of the outlet on the condensate trap. The remaining hose is suffi cient
length to accommodate all furnace orientations.
FIGURE 25
3. A 1/2" PVC coupling or bushing will fi t snug over the 1/2" rubber hose. A 3/4" CPVC coupling or bushing will
fi t snug over the 5/8" rubber hose. This method ensures a water tight seal and also allows the condensate
trap to be easily removed for service.
FIGURE 27
4. If extra security is desired, it is recommended to secure a strip of strapping around the drain. Utilize the
existing condensate trap screws to secure the strapping.
11.6
CONDENSATE NEUTRALIZERS
Some local codes may require the use of a condensate neutralizer. If the furnace condensate is to be routed to
a septic system, it may be advisable to use a condensate neutralizer.
When condensate neutralizers are used, it is advisable to install it with an overfl ow bypass tube.
W415-2379 / B / 09.22.20
FIGURE 24
FIGURE 26
NOTE
If using CPVC piping, connect the
CPVC threaded adapter to the
condensate trap. Adapter provided
in furnace parts baggie.
H16.5.3B
H16.6