6.8 Test leads and probes
The voltage between the connection points of the meter and the earth potential
must not exceed 600 V AC/DC in CAT III.
Probe assemblies to be used for MAINS measurements should meet EN
61010-031 standard, rated CAT III 600 V, 40 A or better.
Risk of electric shock! Use caution when working with voltages above 30 V/AC
rms (42.4 V peak), 60 V/DC.
Test leads must be disconnected before changing the range / function.
The cables have a wear indicator. If damaged, a second insulation layer in a
different colour becomes visible. Do not use if this occurs, replace immediately!
When taking measurements do not grip beyond the finger barrier or grip range
markings on the probes.
When using the probes without cover caps, measurements between the meter
and the earth potential must not be performed above the measuring category
CAT II.
Prevent short circuits by ensuring test points/connections do not touch when
taking measurements.
Always check the probes and leads for any sign of damage before each use.
Do not use if damaged, replace immediately!
44
When taking CAT III measurements, probes
with cover caps (max. 4 mm free contact
length) must be used to avoid accidental
short circuits.