3.2.3 Settings for each type of battery
Type of battery
SW5
TYPE-1 BAT.
Calcium Lead Tin
OFF
(e.g.: Delphi/Delco
Freedom)
TYPE-2 BAT.
OFF
Lead Sealed
TYPE-3 BAT.
Gelled Lead or
OFF
Calcium Lead
TYPE-4 BAT.
Open Lead with
ON
maintenance (free
electrolyte)
WINTERING
for TYPE-1 BAT.
OFF
TYPE-2 BAT.
TYPE-3 BAT.
WINTERING
ON
For TYPE-4 BAT.
(*)Voltage on BAT 1/BAT 2 with 10% of rated current and a tolerance of +/- 1%
Voltage on BAT D = BAT 1 or BAT 2 – approx. 0.4V
3.2.4 Settings
The charger's factory settings are:
TYPE-2 BAT. Sealed Lead (see table above)
BOOST in ON position
The installer should set the switches (excluding input and off-load output voltage) and possibly adjust the output voltage
using potentiometer RV1 accessible from outside at the bottom of the charger (use the appropriate tool to turn the screw
of the potentiometer), depending on:
-
the type of battery (contact the battery manufacturer if necessary)
-
intended usage
-
the cross-section and length of the output cables
-
whether or not the boost function is required
For special batteries, call in a professional installer, who will make the specific settings in accordance with the
accumulator manufacturer's specifications and according to the specifics of the installation.
Cristec disclaims any liability in case of damage to batteries or ineffective recharging.
CPS2OEM25ADEB.doc
All manuals and user guides at all-guides.com
Switch position
SW4
SW3
SW2
15,1V
14,4V
ON
14,3V
13,6V
OFF
14,1V
13,4V
OFF
13,7V
13V
OFF
14,1V
13,4V
OFF
13,7V
13V
OFF
CPS2 OEM 12V/25A
Tension Phase
Boost*
SW1
Boost
15,1V
ON
14,3V
ON
ON
14,1V
ON
13,7V
ON
14,1V
ON
OFF
Tension Phase
Floating*
14,4V
13,6V
13,4V
13V
13,4V
ON
17