Addr
Description
5030
State inverter:
0 = Idle
1 = DC link internal test
2 = DC syncronize to
external voltage
3 = DC link charge
4 = AC syncronize to
external voltage
5 = AC close mains con-
tactor
6 = AC connected
7 = AC open mains con-
tactor
99 = Alarm
100 = Parameter not
valid for chosen module
5031
Indicates the source of
the alarm event:
0 = Idle state
1 = DC link internal test
state
2 = DC syncronize to
external voltage state
3 = DC link charge state
4 = AC syncronize to
external voltage state
5 = AC close mains con-
tactor state
6 = AC connected state
7 = AC open mains con-
tactor state
99 = Alarm state
100 = No alarm present
or parameter not valid for
chosen module
101 = RS-485 master
5032
Voltage at which the
droop control function
delivers the maximum
possible intervention due
to maximum DC-bus vol-
tage.
5033
Voltage at which the
droop control function
starts to intervene due to
a too high DC link vol-
tage.
A67-0141-00.BKfr-0
01-11
Unit
Res
Default
olu-
tion
1.0
100
1.0
100
V
0.1
0
V
0.1
0
2024-08-01
Min
Max
Dat
Typ
atyp
e
e
0
100
UIN
Regi
T16
ster
0
101
UIN
Regi
T16
ster
600
960
UIN
Regi
0
0
T16
ster
600
959
UIN
Regi
0
0
T16
ster
Manipulation
Len
FCr
FCw
gth
1
04
1
04
1
04
1
04
91