Number
Message
50044
Overcurrent balan-
cer RMS
50047
Overvoltage L1
RMS
50048
Overvoltage L2
RMS
50049
Overvoltage L3
RMS
50050
Undervoltage L1
RMS
50051
Undervoltage L2
RMS
50052
Undervoltage L3
RMS
50053
Grid contactor
could not be closed.
50068
Subslave communi-
cation alarm
50069
Master communica-
tion alarm
50080
Overvoltage grid N
to PE
50081
Overvoltage internal
DC link
50082
Overvoltage internal
N to PE
50083
Overvoltage exter-
nal DC link positive
part
50084
Overvoltage exter-
nal DC link nega-
tive part
50085
Overvoltage exter-
nal DC link
50086
Overvoltage exter-
nal DC link mid-
point to PE
50087
Wrong polarity on
DC link detected
50088
Overvoltage exter-
nal 24-V auxiliary
supply
142
Recherche des erreurs
Effect
Cause
Device switches off.
Overcurrent balan-
cer RMS.
No operation pos-
Overvoltage L1
sible.
RMS.
No operation pos-
Overvoltage L2
sible.
RMS.
No operation pos-
Overvoltage L3
sible.
RMS.
No operation pos-
Undervoltage L1
sible.
RMS.
No operation pos-
Undervoltage L2
sible.
RMS.
No operation pos-
Undervoltage L3
sible.
RMS.
No operation pos-
Grid contactor
sible.
could not be closed.
No operation pos-
Subslave communi-
sible.
cation alarm.
No operation pos-
Master communica-
sible.
tion alarm.
No operation pos-
Overvoltage grid N
sible.
to PE.
Device switches off.
Overvoltage internal
DC link.
Device switches off.
Overvoltage internal
N to PE.
Device switches off.
Overvoltage exter-
nal DC link positive
part.
Device switches off.
Overvoltage exter-
nal DC link nega-
tive part.
Device switches off.
Overvoltage exter-
nal DC link nega-
tive part.
Device switches off.
DC link is unsyme-
tric.
Device switches off.
Wrong polarity on
DC link detected.
Device switches off.
Overvoltage exter-
nal 24-V auxiliary
supply.
Action
Contact service.
Check grid settings,
grid voltage L1 and
external devices.
Check grid settings,
grid voltage L2 and
external devices.
Check grid settings,
grid voltage L3 and
external devices.
Check grid settings,
grid voltage L1 and
external devices.
Check grid settings,
grid voltage L2 and
external devices.
Check grid settings,
grid voltage L3 and
external devices.
Check the contac-
tor, delaytime, cabl-
ing, AUX-suppy of
contactor etc.
Check cabling to
subslaves and sys-
tem start-up routine.
Check cabling to
master and system
start-up routine.
Check voltage N to
PE, N and PE con-
nections.
Contact service.
Contact service.
Check DC link vol-
tage and midpoint.
Check DC link vol-
tage and midpoint.
Check DC link vol-
tage and midpoint.
Check DC link vol-
tage and midpoint.
Check DC link pola-
rity.
Check the external
24-V auxiliary sup-
ply.
2024-08-01
A67-0141-00.BKfr-0
Caused
by
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
01-11