Number
Message
50015
Overvoltage DC link
positive part
50016
Overvoltage DC link
negative part
50018
Overcurrent L1
hardware
50019
Overcurrent L2
hardware
50020
Overcurrent L3
hardware
50021
Overcurrent balan-
cer hardware
50024
Overcurrent/short
circuit in island L1
50025
Overcurrent/short
circuit in island L2
50026
Overcurrent/short
circuit in island L3
50030
DC current compo-
nent L1 too high
50031
DC current compo-
nent L2 too high
50032
DC current compo-
nent L3 too high
50033
Grid frequency too
high
50034
Grid frequency too
low
50036
Synchronization to
grid failed.
50037
DC link voltage too
low for operation
50038
DC link unbalanced
50041
Overcurrent L1 RMS
50042
Overcurrent L2 RMS
50043
Overcurrent L3 RMS
A67-0141-00.BKfr-0
01-11
Effect
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
Device switches off.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
Device switches off.
Device switches off.
Device switches off.
2024-08-01
Cause
Action
Overvoltage DC link
Check DC link vol-
positive part.
tage and midpoint.
Overvoltage DC link
Check DC link vol-
negative part.
tage and midpoint.
Overcurrent L1.
Check cabling of
L1, grid voltage
sense lines and AC
contactor.
Overcurrent L2.
Check cabling of
L2, grid voltage
sense lines and AC
contactor.
Overcurrent L3.
Check cabling of
L3, grid voltage
sense lines and AC
contactor.
Overcurrent balan-
Contact service.
cer bridge.
Overcurrent/short
Check loads and
circuit in island L1
fuses in micro-grid.
Overcurrent/short
Check loads and
circuit in island L2
fuses in micro-grid.
Overcurrent/short
Check loads and
circuit in island L3
fuses in micro-grid.
DC current compo-
Contact service.
nent L1 too high.
DC current compo-
Contact service.
nent L2 too high.
DC current compo-
Contact service.
nent L3 too high.
Grid frequency too
Check the grid fre-
high.
quency.
Grid frequency too
Check the grid fre-
low.
quency.
Internal filter capaci-
Check grid settings
tor voltage and grid
and AC-connection
voltage do not line
(alignment of power
up.
and sense lines).
DC link voltage too
Check DC link set-
low for operation.
tings and wiring.
DC link unbalanced.
Check DC link set-
tings and wiring.
Overcurrent L1
Check cabling of
RMS.
L1, grid voltage
sense lines and AC
contactor.
Overcurrent L2
Check cabling of
RMS.
L2, grid voltage
sense lines and AC
contactor.
Overcurrent L3
Check cabling of
RMS.
L3, grid voltage
sense lines and AC
contactor.
Recherche des erreurs
Caused
by
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
141