Télécharger Imprimer la page

Trumpf TruConvert AC 3025 Manuel Opérateur page 145

Masquer les pouces Voir aussi pour TruConvert AC 3025:

Publicité

Messages d'alarme
Number
Message
40300
RS-485 communica-
tion alarm
40301
RS-485 communica-
tion alarm
40302
Active interface
(Modbus or Web-
GUI) communica-
tion timeout has
occured.
40303
RS-485 communica-
tion alarm
40304
No slave module
was found, please
check RS-485 con-
nection(s).
40305
Number of or combi-
nation of connected
slave types not sup-
ported.
40412
Software versions
of system control
and module(s) do
not match.
40413
Software versions
of system control
and module(s) do
not match.
40414
Software versions
of system control
and module(s) do
not match.
40415
Software versions
of system control
and module(s) do
not match.
40416
Software versions
of system control
and module(s) do
not match.
40419
Material numbers of
AC/DC Modules are
wrong or do not
match
40420
Module alarm cau-
sed system transi-
tion to alarm state
A67-0141-00.BKfr-0
01-11
Effect
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
No operation pos-
sible.
System cannot
finish start-up proce-
dure.
System cannot
finish start-up proce-
dure.
System cannot
finish start-up proce-
dure.
System cannot
finish start-up proce-
dure.
System cannot
finish start-up proce-
dure.
System cannot
finish start-up proce-
dure.
System cannot
finish start-up proce-
dure.
No operation pos-
sible.
Entire system chan-
ges into alarm state.
2024-08-01
Cause
Action
Communication pro-
Check RS-485 com-
blem on RS-485
munication.
bus.
Communication pro-
Check RS-485 com-
blem on RS-485
munication.
bus.
Active interface
Check active inter-
(Modbus or Web-
face (Modbus or
GUI) communica-
WebGUI) or disable
tion timeout has
timeout.
occured.
Communication pro-
Check RS-485 com-
blem on RS-485
munication.
bus.
No slave module
Check RS-485 con-
was found.
nection(s) and
modules.
Number of or combi-
Check module confi-
nation of connected
guration. Only
slave types not sup-
homogeneous
ported.
modules are allo-
wed on one
RS-485 bus.
Software versions
Software update
of system control
necessary.
and module(s) do
not match.
Software versions
Software update
of system control
necessary.
and module(s) do
not match.
Software versions
Software update
of system control
necessary.
and module(s) do
not match.
Software versions
Software update
of system control
necessary.
and module(s) do
not match.
Software versions
Software update
of system control
necessary.
and module(s) do
not match.
Material numbers of
Check compatibility
AC/DC modules are
of material numbers.
wrong or do not
match.
Alarm triggered by
Check alarm on
module or submo-
modules or submo-
dule.
dules. Check alarm
policy.
Recherche des erreurs
Caused
by
System
control
System
control
System
control
System
control
System
control
System
control
System
control
System
control
System
control
System
control
System
control
System
control
System
control
139

Publicité

loading