Télécharger Imprimer la page

Trumpf TruConvert AC 3025 Manuel Opérateur page 150

Masquer les pouces Voir aussi pour TruConvert AC 3025:

Publicité

Number
Message
50134
Overload capabilitiy
exceeded
50135
Overcurrent capabili-
tiy exceeded
50138
No country selected
or selected country
does not match
with selected grid
code
50139
DC-DC module
alarm caused transi-
tion to alarm state.
60090
Battery overvoltage
60093
DC link overvoltage
60102
DC link voltage too
low for operation
60132
RS-485 communica-
tion alarm
60142
Battery undervoltage
60145
Wrong polarity on
DC terminal detec-
ted
60168
Ambient tempera-
ture over allowed
range
60186
Ambient tempera-
ture under allowed
range
60192
Fan defective or
stuck
60200
DC-DC Precharge
Conditions could
not be met.
60202
DC-link could not
be charged
60700
Auxiliary supply
overvoltage
60703
Auxiliary supply
undervoltage
Messages d'alarme CA-CC
144
Recherche des erreurs
Effect
Cause
Device switches off.
Overload capabilitiy
exceeded
Device switches off.
Overcurrent capabili-
tiy exceeded
No operation pos-
No country selected
sible.
or selected country
does not match
with selected grid
code.
Entire system chan-
Alarm triggered by
ges into alarm state.
DC-DC module.
No operation pos-
Battery voltage too
sible.
high.
No operation pos-
DC link voltage too
sible.
high.
No operation pos-
DC link voltage too
sible.
low.
No operation pos-
Communication pro-
sible.
blem on RS-485
bus.
No operation pos-
Battery voltage too
sible.
low.
Risk of damaging
Wrong polarity on
hardware.
battery detected.
No operation pos-
Ambient tempera-
sible.
ture over allowed
range.
No operation pos-
Ambient tempera-
sible.
ture under allowed
range.
No operation pos-
Fan is defective or
sible.
stuck.
No operation pos-
Precharge condi-
sible.
tions could not be
met.
No operation pos-
DC link could not
sible.
be charged
Risk of damaging
Auxiliary supply vol-
hardware.
tage too high.
Unstable system.
Auxiliary supply vol-
tage too low.
Action
Reduce load in
island mode opera-
tion.
Reduce load in
island mode opera-
tion.
Select your country.
Check alarm on DC-
DC modules. Check
alarm policy.
Check battery vol-
tage.
Check DC link.
Check DC link pre-
charge.
Check RS-485 com-
munication.
Check battery vol-
tage.
Check battery pola-
rity.
Check the ambient
temperature.
Check the ambient
temperature.
Check fan.
Check droop-mode
settings, DC link
and battery voltage.
Check DC link and
connected compo-
nents.
Check the external
24-V auxiliary sup-
ply.
Check the external
24-V auxiliary sup-
ply.
2024-08-01
A67-0141-00.BKfr-0
Caused
by
AC-DC
module
AC-DC
module
AC-DC
module
AC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
DC-DC
module
Tab. 39